Product Specifications
- Technology: Guided Wave Radar (GWR) based on Time Domain Reflectometry (TDR).
- Power Supply: 24 VDC nominal (Range: 16 to 36 VDC) via a loop-powered system.
- Analog Output: 4–20 mA with digital HART; fully compliant with NAMUR NE43 standard.
- Measuring Range: From 0.15 meters to 30 meters (6 inches to 100 feet).
- Process Temperature: From -196°C to +200°C (-320°F to +400°F).
- Maximum Pressure: Up to 430 bar (6,250 psi), depending on the attached probe model.
- Accuracy: ±3 mm or 0.03% of the measured distance, whichever is greater.
- Display Resolution: Analog output at 0.003 mA; Digital display at 1 mm.
- Safety Ratings: SIL 2 capable (Hardware); FM, CSA, ATEX, IECEx intrinsically safe and explosion-proof.
Technical and Operational Features
- Interchangeable Probes: A single universal transmitter head interfaces with all compatible probe types.
- Advanced Diagnostics: Automated recording of trend data and internal diagnostic echo curves.
- Troubleshooting Display: Onboard LCD screen provides descriptive text errors and immediate corrective actions.
- Overfill-Safe Performance: Coaxial and twin-rod probes enable accurate measurement up to the process seal.
- Dielectric Range: Capable of measuring low dielectric fluids down to 1.4 up to 100.
- Vapor Compensation: Reliable operation in saturated steam or vapor conditions without sensor drift.
- Enclosure Rating: IP66 / NEMA 4X single-compartment housing available in aluminum or stainless steel.