Product Description
- Product Range: Harmony Electromechanical Relays
- Series Name: Miniature
- Product Type: Plug-in relay
- Device Short Name: RXM
- Contacts Type and Composition: 4 C/O (4PDT)
- Control Circuit Voltage: 24 V DC
- [Ithe] Conventional Enclosed Thermal Current: 6 A at -40…55 °C
- Status LED: Without
- Control Type: Lockable test button
- Utilization Coefficient: 20 %
Complementary Specifications
- Shape of Pin: Flat
- [Ui] Rated Insulation Voltage: 250 V conforming to IEC / 300 V conforming to CSA, UL
- [Uimp] Rated Impulse Withstand Voltage: 2.5 kV during 1.2/50 µs
- Contacts Material: AgNi
-
[Ie] Rated Operational Current:
- 3 A at 28 V (DC) NC conforming to IEC
- 3 A at 250 V (AC) NC conforming to IEC
- 6 A at 28 V (DC) NO conforming to IEC
- 6 A at 250 V (AC) NO conforming to IEC
- 6 A at 277 V (AC) conforming to UL
- 8 A at 30 V (DC) conforming to UL
- Maximum Switching Voltage: 250 V conforming to IEC
- Resistive Rated Load: 6 A at 250 V AC / 6 A at 28 V DC
- Maximum Switching Capacity: 1500 VA / 168 W
- Minimum Switching Capacity: 170 mW at 10 mA, 17 V
- Operating Rate: <= 1200 cycles/hour under load / <= 18000 cycles/hour no-load
- Mechanical Durability: 10,000,000 cycles
- Electrical Durability: 100,000 cycles for resistive load
- Average Coil Consumption: 0.9 W
- Drop-out Voltage Threshold: >= 0.1 Uc DC
- Operate Time: 20 ms
- Release Time: 20 ms
- Average Coil Resistance: 650 Ohm at 20 °C +/- 10 %
- Rated Operational Voltage Limits: 19.2...26.4 V DC
- Protection Category: RT I
- Test Levels: Level A group mounting
- Operating Position: Any position
- Net Weight: 0.037 kg
Environment
-
Dielectric Strength:
- 1300 V AC between contacts with micro disconnection
- 2000 V AC between coil and contact
- 2000 V AC between poles
- Product Certifications: CE, UL, CSA, EAC, Lloyd's
- Standards: IEC 61810-1, UL 508, CSA C22.2 No 14
- Ambient Air Temperature for Storage: -40…85 °C
- Ambient Air Temperature for Operation: -40…55 °C
- Vibration Resistance: 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation / 5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
- IP Degree of Protection: IP40 conforming to IEC 60529
- Shock Resistance: 10 gn in operation / 30 gn not operating
- Pollution Degree: 2